Standard Model: VAV – PID – FP
Cosmos parallel fan-powered terminal units are designed to provide superior comfort by intermittent parallel fan operation. Conditioned primary air is varied during cooling while the fan cycles on during heating. Parallel fan-powered terminal units allows for recovery of waste heat from the return plenum and a potential reduction in central fan energy, thereby lowering operating costs.
Cosmos parallel fan-powered terminal units are designed to provide superior comfort by intermittent parallel fan operation. Conditioned primary air is varied during cooling while the fan cycles on during heating. Parallel fan-powered terminal units allows for recovery of waste heat from the return plenum and a potential reduction in central fan energy, thereby lowering operating costs. In the heating mode with fan energized parallel fan-powered terminal units improve air circulation through better diffuser performance.
The primary air valve is sized for cooling demand similar to single duct terminal design requirements.
The recirculating air section is typically sized at 50% of the maximum primary air valve demand which results in lower noise, lower unit cost and reduced energy when compared to constant volume terminals.
Each Price fan powered terminal unit receives a full operational check before shipment and arrives factory calibrated in accordance with project specifications. This means costly labor and setup delays are avoided.
● Recirculating fan section operated only on a demand for heat from the space thermostat.
● Primary air section controls are pressure independent.
● Size 20 and 30 -22 gauge construction (optional 20 gauge available). Size 40-60-20 gauge construction. Zinc-coated steel housing, mechanically sealed ,leak resistant.
● Damper constructed of double layer of 24 gauge galvanized steel with sandwiched flexible gasket to provide tight seal (<1% at 3″ static pressure).
● Factory calibrated controls per each job requirement.
● Cosmos multi-quadrant averaging flow sensor provides highly accurate +/- 5% flow readings after certified balancer has balanced terminal.
● Energy efficient six pole single speed PSC motors with adjustable SCR solid state fan speed controllers are standard.
● Electronically Commutated Motors (ECM) available as an option.
● Single point electrical connections.
● Round inlets available in sizes 150mm through 400mm.
● Rectangular flanged discharge with flange connection
Compact, durable zinc-coated steel casing means reduced ceiling plenum space requirements and protection from corrosion.
Terminal casing is internally lined with fiberglass insulation. The insulation’s high density skin provides erosion resistance while effectively attenuating noise. Insulation meets requirements of UL181 and NFPA-90A
Proven reliable primary air section with heavy gauge damper and low leakage blade seal.
● ECM energy efficient motor option
● Discharge attenuator section (DAS) for reduction of discharge noise
● Inlet attenuator section (IAS) for reduction of radiated noise
● Merv 8 and 13 filter bank for enhanced filtration of recirculated air
● Hanger brackets and spring isolation
● Auto reset thermal cutout (one per element)
● 80/20 Nickel chrome heating elements.
● Airflow safety switch
● Flange Connection
● Control transformer for DDC or Analog electric controls
● Fan relay for DDC fan terminals
● Modulating heating control
● Manual reset thermal cutout as optional